Low-temperature Monoblock Type HLRVE-15/2
- Multi-stage inverter heat pump technology is the breakthrough for the ultra-low temperature heating limitation of traditional heat pump technology. It solves problems of much low-temperature heating attenuation, low energy efficiency and other technical troubles for ordinary heat pump. It greatly broadens the ambient temperature range of machine operation (form -30℃ to 54℃) and considerably improves low-temperature heating capacity. Compared to central heating system, energy consumption can be reduced by more than 40% every time. And it creatively improved the coal-fired pollution of northern China in winter which based on ensuring comfort and economy.
-
Parameter Sheet
-
System Diagram
-
Size Chart
-
Installation Drawing
Model |
HLRVE-15/2(Monoblock type) |
|||
/ |
Cooling |
Heating |
Hot water |
|
Rated cooling(heating) Capacity |
kW |
14 |
17 |
16 |
Power Supply |
V/Ph/Hz |
220/1/50 |
||
Rated Power |
kW |
4.76 |
4.68 |
5.4 |
Rated Current |
A |
22.8 |
22.4 |
25.9 |
COP |
W/W |
2.94 |
3.63 |
2.96 |
Compressor Amount |
set |
1 |
||
Compressor Type |
/ |
Two-stage inverter compressor specialized for heat pump |
||
Fan Amount |
set |
1 |
||
Operation Noise |
Db(A) |
51 |
||
Water Connector Size |
/ |
DN32 |
||
Structure Type |
/ |
Side Wind |
||
Operation Ambient Temperature |
/ |
-30℃~54℃ Ultra Low Temperature Type |
||
Water Flow |
M³/h |
2.9 |
||
Refrigerant |
/ |
R410A |
||
NW/GW |
Kg |
165/190 |
||
Machine Size (L/W/H) |
mm |
1115/425/1270 |
||
Package Size (L/W/H) |
mm |
1170/510/1430 |